BOA-Control/ BOA‑Control IMS Globe valve

Globe valve BOA-Control/ BOA‑Control IMS

Balancing, measurement and shut-off valve with flanged ends to DIN/EN, constant measurement accuracy independent of differential pressures. Body in standard face-to-face length to EN 558/1, throttling plug, scaled position indicator, travel stop and insulating cap with anti-condensation feature; maintenance-free, full insulation possible. Also available with electrostatic plastic coating (EKB) and DVGW-certified for drinking water. With integrated ultrasonic sensors not coming into contact with the fluid handled. Stationary monitoring by means of BOATRONIC 100 MOD (24 V AC/DC, Modbus) of flow direction, volume flow rate and temperature, and optional recording of supply and return temperature as well as thermal output and quantity of heat. Mobile measurement of flow direction, volume flow rate and temperature using the BOATRONIC MS (battery powered) / BOATRONIC 100 (rechargeable battery powered) measuring computers.
Lihat semua dokumen dan unduhan

Aplikasi utama

  • Hot-water heating systems
  • Air-conditioning systems
  • Cooling circuits
  • Local heating and district heating

Data teknis

Nominal pressure Hydr casing
PN 16
Maximum nominal size TSG
DN 350
Max allowed fluid temp TSG
120 °C

Your KSB contact: We’re here to support you

Do you need any assistance finding the right material number?
We’ll soon provide a list so you can directly place your purchase order.
Meanwhile please contact our support:

Your local contact


Kontak KSB: Kami ada untuk Anda

Manfaat

  • 1 valve with 4 functions: shut-off, control, measurement and monitoring by integrated ultrasound measurement system and EPDM-encapsulated throttling plug with linear characteristic curve
  • BOA-Control is ideally suited for use in heating systems.
  • BOA-Control IMS is suitable for universal use in heating and cooling systems and as a permanent measurement valve.

Sertifikat

  • B05B_22307435275-1_1
    Approved in accordance with German drinking water regulation
    Germany

Data teknis

Component function
Shut off/control flow
Connection type Inlet
Flange
Design concept Drive
With electric actuator,
With handwheel
Mtrl Hydraulic casing
EN-GJL-250,
EN-GJS-400-18-LT,
EN-GJL-250-EKB
Nominal pressure Hydr casing
PN 16
Maximum nominal size TSG
DN 350
Minimum nominal size TSG
DN 15
Max allowed fluid temp TSG
120 °C
Min allowed fluid temp TSG
-10 °C

Gambar penampang