Main Applications
- Handling clean or aggressive fluids not chemically and mechanically aggressive to the pump materials.
- Water supply systems
- Cooling circuits
- Swimming pools
Technical Data
- Maximum flow rate TSG
- 1368 m3/h
- Maximum head TSG
- 160 m
- Max allow ds work.pressure TSG
- 16 bar
- Max allowed fluid temp TSG
- 140 °C
Benefits
- Improved efficiency and NPSHreq by experimentally verified hydraulic design of impellers (vanes)
- Operating costs reduced by trimming the nominal impeller diameter to match the specified duty point
- Little wear, low vibration levels and excellent smooth running characteristics thanks to good suction performance and virtually cavitation-free operation across a wide operating range
Technical Data
- Component function
- Pump
- Connection type Inlet
- Flange
- Drive concept
- With electric actuator,
Combustion engine - Maximum flow rate TSG
- 1368 m3/h
- Minimum flow rate TSG
- 1.5 m3/h
- Maximum head TSG
- 160 m
- Minimum head TSG
- 2 m
- Mains frequency
- 50 Hz,
60 Hz - Mains voltage
- 400 V,
460 V,
220 V,
230 V,
240 V,
380 V,
415 V,
500 V,
575 V,
660 V,
690 V - Mtrl Hydraulic casing
- EN-GJL-250/A48 CL 35B,
CC480K-GS/B30 C90700,
1.4408/A743CF8M,
EN-GJS-400-15/A536 GR 60-40-18 - Nominal pressure Outlet
- PN 16,
PN 10,
CL 150,
CL 125 - Max allow ds work.pressure TSG
- 16 bar
- Suction behaviour
- Non-self-priming
- Max allowed fluid temp TSG
- 140 °C
- Min allowed fluid temp TSG
- -30 °C